/> I'm having a 2.2KV APC UPS, and i'm connecting my Gentoo email server on it, |
2 |
> so what is the proper way to configure my server to auto shutdown, when the |
3 |
> Main power off. |
4 |
|
5 |
|
6 |
emerge apcupsd |
7 |
|
8 |
It works beautifully. :-) Communication between server and UPS works with serial and USB. I |
9 |
purchased the additional SNMP card with mine and it works also. |
10 |
|
11 |
To have a stable system, you will need to: |
12 |
1) alter your bios so that your server will automatically start up on power restore. |
13 |
2) Adjust apcupsd.conf to match your server(s) power down requirements. |
14 |
3) Follow the apcupsd power failure test procedure to insure your server issues a UPS power down |
15 |
w/delay command during server halt to protect against intermittent power failures. |